[1]王文启,张磊,李京校.2010-2016年北京市大中小学校避雷装置隐患分析及对策[J].气象研究与应用,2018,39(01):124-127.
 Wang Wenqi,Zhang Lei,Li Jingxiao.Analysis on the hidden dangers of lightning arresters in colleges and schools in Beijing from 2010 to 2016 and corresponding countermeasures[J].Journal of Meteorological Research and Application,2018,39(01):124-127.
点击复制

2010-2016年北京市大中小学校避雷装置隐患分析及对策()
分享到:

气象研究与应用[ISSN:1673-8411/CN:45-1356/P]

卷:
第39卷
期数:
2018年01期
页码:
124-127
栏目:
大气监测与装备技术
出版日期:
2018-03-31

文章信息/Info

Title:
Analysis on the hidden dangers of lightning arresters in colleges and schools in Beijing from 2010 to 2016 and corresponding countermeasures
作者:
王文启 张磊 李京校
北京市气象灾害防御中心, 北京 100089
Author(s):
Wang Wenqi Zhang Lei Li Jingxiao
Beijing Meteorological Disaster Prevention Center, Beijing 100089
关键词:
北京市校园防雷隐患对策
Keywords:
Beijingcampushidden dangers of lightning protectioncountermeasures
分类号:
P427
摘要:
对2010-2016年北京市100所大中小学校避雷装置检测情况进行分析,结果表明:100所大中小学校防雷隐患出现频率最高的依次是:未安装电涌保护装器(损坏)占73%;内(外)设备未接地占62%;等电位连接(电位连接网络相连)占41%;避雷带捆绑现象占30%;无直击雷防护装置占21%;架空飞线、避雷带倒伏、未用跨接、避雷带不能对建筑物进行全面防护(不在直击雷保护范围内)各占17%;接地引下线根数(地阻值超标、过大、断开)、避雷带断开各占11%。按规范要求,提出安全可行、有针对性的整改意见和对策措施,以便为学校完善校园防雷设施和强化其防雷安全工作提供参考。
Abstract:
In this paper, the detection of lightning arresters in 100 colleges, primary and secondary schools in Beijing from 2010 to 2016 was analyzed. The results showed that the frequencies of lightning protection hidden dangers in 100 primary and secondary schools were the following:uninstalled surge protective device(damage)accounted for 73%, unearthed internal(outside)equipment was 62%, equipotential connection(potential connection network)accounted for 41%, lightning belt binding phenomenon accounted for 30%, no direct lightning protection device accounted for 21%; overhead flying line, the arrester belt lodging, unused cross connection and lightning belt failing to protect the building completely(not in the protection range of direct lightning) accounted for 17%, respectively; the number of the earth connecting cable(ground resistance overproof, oversize, or disconnection)and the breaking of the lightning belt each accounted for 11%. Hence, based on the requirements of the standard, safe, feasible, and pertinent rectification opinions and countermeasures are put forward to provide a reference for schools to improve the campus lightning protection facilities and strengthen their lightning protection work.

参考文献/References:

[1] 郑育群,符晓虹.文昌市雷暴气候统计特征[J].气象研究与应用,2008,29(4):72-73.
[2] 李京校,李家启,肖稳安,等. 重庆市雷暴气候变化特征分析[J].热带地理,2011,31(2):171-177.
[3] 吕禄,徐式强,蒋发壮. 学校教学楼的防雷保护[J].气象研究与应用,2009,30(S2):196-197,199.
[4] 李宏景.百色市右江区中小学校防雷工作探讨[J].气象研究与应用,2012,33(S2):125,128.
[5] 蔡云泉,路明.关于中小学校防雷工作的探讨[C].第26届中国气象学会年会公共气象服务论坛,杭州,2009,227-231.
[6] 李京校,程云峰.漯河市中小学校防雷现状与对策[C].2007年,广州,第六届中国国际防雷论坛:37-38.
[7] 吕锡焕,丘志彪.浅谈学校电教室防雷[J].气象研究与应用,2011,32(4):94-96.
[8] 李京校,钱慕晖,李如箭,等. 北京市雷击人身伤亡事故特征及防雷装置研究[J].中国农学通报,2016,32(29):161-168.
[9] 钱慕晖,李京校,李如箭,等. 2005-2014年北京市雷电灾害特征分析[J].气象与环境科学. 2016,32(4):127-132.
[10] 林海滨.完善建筑物内部防雷装置设计的实践经验.气象研究与应用,2007,28(3):56-58,72.
[11] 赵玉红,黄云清,王熙军.加强农村中小学校防雷工作的思考[J].气象研究与应用,2010,31(2):74-75.
[12] 李宁,胡泉,李莹.等电位连接在现代建筑物防雷中的重要性[J].气象研究与应用,2007,28(4):62-63.

备注/Memo

备注/Memo:
收稿日期:2017-06-03。
作者简介:王文启(1959-),男,助理工程师,从事防雷技术工作。Email:279733441@QQ.com
更新日期/Last Update: 1900-01-01